Product and solutions
Double Cabin Outdoor Cabinet
Structure and Layout
Features
• Modularization design
• Flexible and easy to acquire site
• Carrier-class design and reliability
• Subdivision temperature control help to save energy
Value of Customer
• Rapid deployment, rapid establishment
• Saving land resource
• Saving maintenance cost
• Reducing site energy consumption
Mechanical parameters
Description |
Value |
External dimensions of the cabinet |
2100mm(H) × 905mm (W) × 1135mm (D) |
Internal dimensions of the cabinet |
1800mm (H) ×800mm (W) ×800mm (D) |
Base Size |
200mm (H) × 900mm (W) ×900mm (D) |
Weight |
200KG (excluding devices and batteries) |
Wall thickness |
45mm |
Configuration list
Cabinet parameters |
||||||||||||||
User space |
Equipment compartment |
Battery compartment |
||||||||||||
11U power supply space, 10U reserved device space |
2*8U,12V 150AH battery(2 string) |
|||||||||||||
Protection class |
IP55 |
|||||||||||||
Working temperature and humidity |
-40~50(℃), 5% ~100% (20 ℃ ± 5 ℃) |
|||||||||||||
Storage temperature |
-40~70(℃) |
|||||||||||||
Atmospheric pressure |
62KPa~106KPa |
|||||||||||||
The shipping form |
Container transportation |
|||||||||||||
Power Information(Optional) |
||||||||||||||
capacity |
200A |
300A |
600A |
|||||||||||
Power standard |
Three-phase 380V 220V single phase compatible |
|||||||||||||
The output voltage |
220V / 380V, 45Hz ~65Hz |
|||||||||||||
Height |
5~9U |
9~11U |
10~13U |
|||||||||||
Lightning Performance |
Class B + C Class AC, DC level D |
|||||||||||||
The capacity of the power supply module |
50A |
50A |
50A |
|||||||||||
Power Module Number |
2-4 |
2-6 |
2 to 12 |
|||||||||||
Efficiency Power Module |
0.92 / 0.96 |
0.92 / 0.96 |
0.92 / 0.96 |
|||||||||||
AC input CB |
63A / 3P × 2 mechanically interlocked |
100A / 3P × 2 mechanically interlocked |
||||||||||||
AC output breaker |
32A / 1P × 2 10A / 1P × 2 |
32A / 1P × 4 |
||||||||||||
DC output breaker |
LLVD: 32A / 1P × 3,20A / 1P× 10 BLVD: 16A / 1P × 3 |
LLVD: 125A / 1P × 4 BLVD: 63A / 1P × 4,16A / 1P × 2 |
LLVD: 125A / 1P × 3 BLVD: 63A / 1P × 3,16A / 1P × 3 |
|||||||||||
Battery breaker |
125A / 1P × 4 |
|||||||||||||
Temperature control equipment(Optional) |
||||||||||||||
Item |
80W heat exchanger |
190W heat exchanger |
1500W air conditioning |
500W air conditioning |
200W Semiconductor air conditioning |
|||||||||
Setting position |
Equipment compartment |
Equipment compartment |
Equipment compartment |
Battery compartment |
Battery compartment |
|||||||||
Key parameter |
Power standard: DC-48V Heat transfer efficiency: 80W / K |
Power standard: DC -48V Heat transfer efficiency: 190W / K |
Power standard: AC 220V Cooling Efficiency: 1500W |
Power standard: AC 220V Cooling Efficiency: 500W |
Power standard: DC -48V Cooling Efficiency: 200W |
|||||||||
Wiring unit(Optional) |
||||||||||||||
Project |
ODF |
ODF |
||||||||||||
Parameter |
12 core, 19inch 1U,The front line, Connector type : SC / FC |
24 core, 19inch 2U,The front line, Connector type : SC / FC |
||||||||||||
Other information |
||||||||||||||
Working light |
-48V LED lights |
|||||||||||||
Safety standard |
IEC / EN / UL 60 950 |
|||||||||||||
EMC standards |
EN 300 386-2 |
|||||||||||||
Cabinet certification |
Tell Certification |
|||||||||||||
Customer demand Remark |
||||||||||||||
project |
Cabinet height |
Temperature control equipment |
Power system |
Monitoring system |
Wiring unit |
Battery |
Remark |
|||||||
Customer demand |
|
|
|
|
|
|
|