Product and solutions
Outdoor power cabinet
Structure and layout
Features
• Modularization design
• Flexible, easy to get sites
• Carrier-class design and reliability
• Subdivision temperature control, energy saving
value of customer
• Rapid deployment, rapid establishment
• Saving land resource
• Saving maintenance cost
• Reduce site energy consumption
Mechanical parameters
project |
parameter |
External dimensions of the cabinet |
2110mm (H) × 905mm (W) × 1135mm (D) |
Internal dimensions of the cabinet |
1800mm (H) × 800mm (W) × 800mm (D) |
Base Size |
200mm (H) × 900mm (W) × 900mm (D) |
Weight |
≤180KG |
Wall thickness |
45mm |
Protection class |
IP55 |
Working temperature and humidity |
-40 ~ 50 (℃), 5% ~ 100% (20 ℃ ± 5 ℃) |
Storage temperature |
-40 ~ 70(℃) |
Atmospheric pressure |
62KPa ~ 106KPa |
The shipping form |
Container transportation |
Configuration list
Cabinet parameters |
|||||||||
User space |
Power supply area |
||||||||
13U power supply space, 24U reserved device space |
|||||||||
Power System Information(Optional) |
|||||||||
Capacity |
200A |
300A |
600A |
||||||
Power standard |
Three-phase 380V, 220V single phase (compatible) |
||||||||
The output voltage |
220V / 380V, 45Hz ~ 65Hz |
||||||||
Height |
5~9U |
9~11U |
10~13U |
||||||
Lightning Performance |
AC Class B + C, DC Class D |
||||||||
The capacity of the power supply module |
50A |
50A |
50A |
||||||
Power Module Number |
2-4 |
2-6 |
2 to 12 |
||||||
Efficiency Power Module |
0.92 / 0.96 |
0.92 / 0.96 |
0.92 / 0.96 |
||||||
AC input CB |
63A / 3P × 2 mechanically interlocked |
100A / 3P × 2 mechanically interlocked |
|||||||
AC output breaker |
32A / 1P × 2 10A / 1P × 2 |
32A / 1P × 4 |
|||||||
DC output breaker |
LLVD: 32A / 1P × 3,20A / 1P× 10 BLVD: 16A / 1P × 3 |
LLVD: 125A / 1P × 4 BLVD: 63A / 1P × 4,16A / 1P × 2 |
LLVD: 125A / 1P × 3 BLVD: 63A / 1P × 3,16A / 1P × 3 |
||||||
Battery breaker |
125A / 1P × 4 |
||||||||
Temperature control equipment |
|||||||||
project |
80W heat exchanger |
190W heat exchanger |
1500W air conditioning |
||||||
Application space |
Equipment compartment/power compartment |
Equipment compartment/power compartment |
Equipment compartment/power compartment |
||||||
key parameter |
Power standard: DC -48V Heat transfer efficiency: 80W / K |
Power standard: DC -48V Heat transfer efficiency: 190W / K |
Power standard: AC 220V Cooling Efficiency: 1500W |
||||||
Flashlight |
-48V LED lights |
||||||||
Cabinet certification |
Tell Certification, EN 300 386-2, IEC / EN / UL 60 950 |
||||||||
Customer demand Remark |
|||||||||
Project |
Cabinet height |
Temperature control equipment |
Power system |
Monitoring system |
Wiring unit |
Battery |
Remark |
||
Customer demand |
|
|
|
|
|
|
|